Select Your Business Location
For a better experience, please choose where your company is located:
Contact us without obligation
The Gas-Pro PID gas detector gives you full flexibility to monitor a wide range of gas types and volatile organic compounds (VOCs), perfect for environments with high solvent use. Offering both pumped and diffusion solutions, the Gas-Pro PID offers multiple uses within one compact detector, making it suitable across a wide range of applications.
When working in environments with high in levels of solvents, glues, paints and general volatile organic compounds (VOCs), keeping a close eye on your exposure, gas build up and any potential leaks is vital.
The Gas-Pro PID VOC monitor uses Photo Ionization Detection (PID) technology to allow you to detect hundreds of VOCs, monitoring your safety. With its dual-coloured display, the monitor will alert the user with its 95db audible alarm and its dual-coloured visual alarm bars, so you can respond quickly when it counts.
Crowcon’s PID works with a 10.6 electron volt lamp. This sensor is the most stable sensor on the market, providing detection of a wide range of VOCs. The sensor has an internal UV light source, which the gas sample passes through. An electron is released for gases with an ionization potential of 10.6.
PID Technology
Specifications
Size | 43 x 130 x 84mm (1.7 x 5.1 x 3.3ins) |
Weight | 309g 4 gas (10.8oz)/ 340g pumped (11.9oz) 333g 5 gas (11.7oz)/ 362g pumped (12.7oz) |
Alarms | Audible >95dB @ 30cm (98dB @30cm in loud mode) Visual – all angle dual red/blue LEDs Vibrating alert |
Display | Top mount for ease of view with dual colour backlight (green/red) |
Data logging | 125hrs at 10-second intervals (45,000 logs) |
Event logging | Alarm, over range, calibration, bump, on/off, TWA, 1000 events |
Battery | Rechargeable Li-ion, >14 hours (13 hours pumped operation) based on CH4, O2, H2S, CO Typical charge time 7.5 hours |
Sampling | Internal pump as option |
Operating temperature | -20°C to +55°C (-4°F to +131°F) |
Storage | -25°C to +65°C (-13°F to +149°F) |
Humidity | 10 to 95% RH |
Ingress protection | Independently tested to IP65 |
Approvals | IECEx: Ex db ia IIC T4 Gb Tamb -20°C to +55°C ATEX and UKCA: II 2 G Ex db ia IIC T4 Gb Tamb -20°C to +55°C UL: Class 1, Division 1, Groups A, B, C, and D UL 913, UL 60079-0 and UL 60079-11 INMETRO: Ex db ia IIC T4 Gb Tamb -20°C to +55°C Marine Equipment Directive: MED 1500009 |
Compliance | FCC and CE Complies with EMC Directive 2014/30/EU EN50270 and ICES-003 |
Interface | Data connection for gas test solutions and direct to PC |
Charging | Direct connection to multiregional power supply Vehicle charger adaptor Desktop cradle USB power and communications lead |
Crowcon Connect Compatible? | Yes |
Gases and Ranges
Gas | Range | Typical Alarms | Resolution |
PID | 0-1000 ppm | 50 ppm | 1 ppm |
Ammonia (NH3) | 0-100 ppm | 25 ppm | 1 ppm |
Ammonia (NH3) | 0-1000 ppm | N/A | 1 ppm |
Carbon dioxide (CO2) | 0-5% vol. | 0-5% vol. | 0.01% vol. |
Carbon monoxide (CO) | 0-2000 ppm | 20 ppm | 1 ppm |
Carbon monoxide (CO) | 0-500 ppm | 20 ppm | 1 ppm |
Carbon monoxide (hydrogen filtered) |
0-2000 ppm | 20 ppm | 1 ppm |
Chlorine (Cl2) | 0 – 5 ppm | 0.5 ppm | 0.1 ppm |
Dual toxic (CO-H2S) | H2S 0-100ppm CO 0-500ppm |
5 ppm 20 ppm |
1 ppm 1 ppm |
Flammable | 0-100% LEL | 20% LEL | 1% LEL |
Hydrogen (H2) | 0-1000 ppm | N/A | 1 ppm |
Hydrogen sulphide (H2S) | 0-100 ppm | 5 ppm | 1 ppm |
Nitrogen dioxide (NO2) | 0-20 ppm | 1 ppm | 0.5 ppm |
Oxygen (O2) | 0-25% vol. | 19% / 23% vol. | 0.1% vol. |
Ozone (O3) | 0-1 ppm | 0.1 ppm | 0.01 ppm |
Sulphur dioxide (SO2) | 0-20 ppm | 1 ppm | 0.1 ppm |
Chlorine dioxide (ClO2) | 0-1 ppm | 0.1 ppm | 0.1 ppm |
Nitric oxide (NO) | 0-100 ppm | 25 ppm | 1 ppm |